The Fuse Only Blows When You Leave - Short #307

· 15 min

Notas do episódio

In this short podcast episode, Bryan talks about the fuse that only blows when you leave. The service call usually goes like this: you replace a blown fuse, the system runs fine, you leave, and then the fuse blows again. There could be several causes of a blown fuse.
First, ask what was happening right before the system stopped, such as if the unit was starting up, if it was raining outside, or if the operating mode changed. The customer may not know the specifics, but they may be able to offer a clue. If the control fuse blows during a specific call, we may be able to locate a short in one of the circuits involved. We may also be able to find out a bit by inspecting places where wire often gets damaged, such as common points where conductors pinch or rub.
Isolation diagnosis can help us isolate the specific circuit or component with a problem. First, look at the wiring diagram, label conductors, and take pictures of the original setup before disconnecting anything. Keep the correct fuse protection instead of using a larger fuse, leave all safety controls in the circuit, and use the manufacturer's test procedure if it's available. Then, isolate different loads and conductors so they can be energized individually; some modern thermostats make this easy. Also note that continuity testing alone isn't always reliable for locating problematic paths.
Sometimes, motion (from motors), temperature, and moisture can also contribute to intermittent issues. Additionally, some inductive loads, like contactor coils, experience unique intermittent issues that cause the components to draw high current; inductive reactance matters. Measuring current on the different circuits as you energize them can also point you toward circuits that have higher current than expected.
Once you've found and repaired something, go back to the condition that made it fail. Make sure you fix the underlying problem, such as exposure to excess heat, vibration, or moisture.
This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, Fieldpiece, TruTech Tools, and Filtrete.
Resources

• Isolation Diagnosis (tech tip)
• HVAC - Isolate to Diagnose (video)
• HVAC School calculators
• Submit a podcast question
• Learn about the GRIT Foundation
Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.

Site: hvacschool.libsyn.com

Ao vivo, última hora: 9.679 músicas em 4.778 rádios de 137 países

Descubra o mundo pelo rádio

Mais formas de descobrir (7)

Ouviu algo legal? Salve ou abra direto no Spotify.

★ Artista da semana A maior subida na rádio esta semana
A tua música aqui? Desde € 9 por semana →
Hits101 RadioContinuar ouvindo